IEC TS 61724-2:2025

IEC TS 61724-2:2025

septembre 2025
Spécification technique En vigueur

Photovoltaic system performance - Part 2: Power performance index and capacity evaluation method

IEC TS 61724-2:2025 applies to grid-connected PV systems comprising at least one inverter.The test evaluates the PV system only in conditions where output is unconstrained by limitations in AC power output from the inverters. This document defines a test of a PV system's power performance index (PPI). PPI, defined in IEC 61724‑1, is the ratio of a system's measured power output under test conditions to its expected output at those conditions based on the system's design.The test is intended to be performed over a short period of typically three to five days and is typically used to satisfy a contractual performance guarantee as part of the final completion of a PV power plant. This second edition cancels and replaces the first edition published in 2016. This edition includes the following significant technical changes with respect to the previous edition:a) Adapting the document for bifacial PV systems, in accordance with the latest edition of IEC 61724‑1 and current industry practices.b) Adapting the test procedure to account for the limited times of unconstrained system operation which are now common because of high DC-to-AC ratios (clipping) and interconnection limits (curtailment).c) Adapting the test procedure to achieve a test that can be performed in a short time of three to five days during favourable conditions.d) Focusing the document more heavily on the use of modern PV system modelling software to obtain the expected performance of the system under test.e) Simplifying the mathematical procedure for calculating the test results.f) Clearly identifying test elections (optional choices to be made in conducting the test) and providing a template for documenting these elections.g) Clarifying the discussion of the test boundary that separates tested variables from untested variables.h) Expanding and clarifying the discussion of data filtering.

Informations générales

Collections

Normes internationales IEC

Date de publication

septembre 2025

Nombre de pages

26 p.

Référence

IEC TS 61724-2:2025

Numéro de tirage

2
Résumé
Photovoltaic system performance - Part 2: Power performance index and capacity evaluation method

IEC TS 61724-2:2025 applies to grid-connected PV systems comprising at least one inverter.
The test evaluates the PV system only in conditions where output is unconstrained by limitations in AC power output from the inverters. This document defines a test of a PV system's power performance index (PPI). PPI, defined in IEC 61724‑1, is the ratio of a system's measured power output under test conditions to its expected output at those conditions based on the system's design.
The test is intended to be performed over a short period of typically three to five days and is typically used to satisfy a contractual performance guarantee as part of the final completion of a PV power plant. This second edition cancels and replaces the first edition published in 2016. This edition includes the following significant technical changes with respect to the previous edition:
a) Adapting the document for bifacial PV systems, in accordance with the latest edition of IEC 61724‑1 and current industry practices.
b) Adapting the test procedure to account for the limited times of unconstrained system operation which are now common because of high DC-to-AC ratios (clipping) and interconnection limits (curtailment).
c) Adapting the test procedure to achieve a test that can be performed in a short time of three to five days during favourable conditions.
d) Focusing the document more heavily on the use of modern PV system modelling software to obtain the expected performance of the system under test.
e) Simplifying the mathematical procedure for calculating the test results.
f) Clearly identifying test elections (optional choices to be made in conducting the test) and providing a template for documenting these elections.
g) Clarifying the discussion of the test boundary that separates tested variables from untested variables.
h) Expanding and clarifying the discussion of data filtering.
Normes remplacées (1)
IEC TS 61724-2:2016
octobre 2016
Spécification technique Annulée
Photovoltaic system performance - Part 2: Capacity evaluation method

IEC TS 61724-2:2016(E) defines a procedure for measuring and analyzing the power production of a specific photovoltaic system with the goal of evaluating the quality of the PV system performance. The test is intended to be applied during a relatively short time period (a few relatively sunny days). The intent of this document is to specify a framework procedure for comparing the measured power produced against the expected power from a PV system on relatively sunny days.