ISO 52016-1:2017
Energy performance of buildings - Energy needs for heating and cooling, internal temperatures and sensible and latent heat loads - Part 1: Calculation procedures
ISO 52016-1:2017 specifies calculation methods for the assessment of:a) the (sensible) energy need for heating and cooling, based on hourly or monthly calculations;b) the latent energy need for (de-)humidification, based on hourly or monthly calculations;c) the internal temperature, based on hourly calculations;d) the sensible heating and cooling load, based on hourly calculations;e) the moisture and latent heat load for (de-)humidification, based on hourly calculations;f) the design sensible heating or cooling load and design latent heat load using an hourly calculation interval;g) the conditions of the supply air to provide the necessary humidification and dehumidification.The calculation methods can be used for residential or non-residential buildings, or a part of it, referred to as "the building" or the "assessed object".ISO 52016-1:2017 also contains specifications for the assessment of thermal zones in the building or in the part of a building. The calculations are performed per thermal zone. In the calculations, the thermal zones can be assumed to be thermally coupled or not.The calculation methods have been developed for the calculation of the basic energy loads and needs, without interaction with specific technical building systems, and for the calculation of the system specific energy loads and needs, including the interaction with specific systems. The hourly calculation procedures can also be used as basis for calculations with more extensive system control options.ISO 52016-1:2017 is applicable to buildings at the design stage, to new buildings after construction and to existing buildings in the use phase.NOTE Table 1 in the Introduction shows the relative position of ISO 52016-1:2017 within the set of EPB standards in the context of the modular structure as set out in ISO 52000-1.
ISO 52016-1:2017 specifies calculation methods for the assessment of:
a) the (sensible) energy need for heating and cooling, based on hourly or monthly calculations;
b) the latent energy need for (de-)humidification, based on hourly or monthly calculations;
c) the internal temperature, based on hourly calculations;
d) the sensible heating and cooling load, based on hourly calculations;
e) the moisture and latent heat load for (de-)humidification, based on hourly calculations;
f) the design sensible heating or cooling load and design latent heat load using an hourly calculation interval;
g) the conditions of the supply air to provide the necessary humidification and dehumidification.
The calculation methods can be used for residential or non-residential buildings, or a part of it, referred to as "the building" or the "assessed object".
ISO 52016-1:2017 also contains specifications for the assessment of thermal zones in the building or in the part of a building. The calculations are performed per thermal zone. In the calculations, the thermal zones can be assumed to be thermally coupled or not.
The calculation methods have been developed for the calculation of the basic energy loads and needs, without interaction with specific technical building systems, and for the calculation of the system specific energy loads and needs, including the interaction with specific systems. The hourly calculation procedures can also be used as basis for calculations with more extensive system control options.
ISO 52016-1:2017 is applicable to buildings at the design stage, to new buildings after construction and to existing buildings in the use phase.
NOTE Table 1 in the Introduction shows the relative position of ISO 52016-1:2017 within the set of EPB standards in the context of the modular structure as set out in ISO 52000-1.
ISO 13790:2008 gives calculation methods for assessment of the annual energy use for space heating and cooling of a residential or a non-residential building, or a part of it, referred to as “the building”. This method includes the calculation of: the heat transfer by transmission and ventilation of the building zone when heated or cooled to constant internal temperature; the contribution of internal and solar heat gains to the building heat balance; the annual energy needs for heating and cooling, to maintain the specified set-point temperatures in the building – latent heat not included; the annual energy use for heating and cooling of the building, using input from the relevant system standards referred to in ISO 13790:2008 and specified in Annex A. ISO 13790:2008 also gives an alternative simple hourly method, using hourly user schedules (such as temperature set-points, ventilation modes or operation schedules of movable solar shading). Procedures are given for the use of more detailed simulation methods to ensure compatibility and consistency between the application and results of the different types of method. ISO 13790:2008 provides, for instance, common rules for the boundary conditions and physical input data irrespective of the calculation approach chosen. ISO 13790:2008 has been developed for buildings that are, or are assumed to be, heated and/or cooled for the thermal comfort of people, but can be used for other types of building or other types of use (e.g. industrial, agricultural, swimming pool), as long as appropriate input data are chosen and the impact of special physical conditions on the accuracy is taken into consideration. The calculation procedures in ISO 13790:2008 are restricted to sensible heating and cooling. The energy use due to humidification is calculated in the relevant standard on the energy performance of ventilation systems, as specified in Annex A; similarly, the energy use due to dehumidification is calculated in the relevant standard on the energy performance of space cooling systems, as specified in Annex A. ISO 13790:2008 is applicable to buildings at the design stage and to existing buildings. The input data directly or indirectly called for by ISO 13790:2008 should be available from the building files or the building itself. If this is not the case, it is explicitly stated at relevant places in ISO 13790:2008 that it may be decided at national level to allow for other sources of information. In this case, the user reports which input data have been used and from which source. Normally, for the assessment of the energy performance for an energy performance certificate, a protocol is defined at national or regional level to specify the type of sources of information and the conditions when they may be applied instead of the full required input.
ISO 13791:2011 specifies the assumptions, boundary conditions, equations and validation tests for a calculation procedure, under transient hourly conditions, of the internal temperatures (air and operative) during warm periods, of a single room without any cooling/heating equipment in operation.
ISO 13792:2011 specifies the required input data for simplified calculation methods for determining the maximum, average and minimum daily values of the operative temperature of a room in warm periods: a) to define the characteristics of a room at the design stage in order to avoid overheating in summer; b) to define whether the installation of a cooling system is necessary or not.
The Requirements department helps you quickly locate within the normative text:
- mandatory clauses to satisfy,
- non-essential but useful clauses to know, such as permissions and recommendations.
The identification of these types of clauses is based on the document “ISO / IEC Directives, Part 2 - Principles and rules of structure and drafting of ISO documents ”as well as on a constantly enriched list of verbal forms.
With Requirements, quickly access the main part of the normative text!

COBAZ is the simple and effective solution to meet the normative needs related to your activity, in France and abroad.
Available by subscription, CObaz is THE modular solution to compose according to your needs today and tomorrow. Quickly discover CObaz!
Request your free, no-obligation live demo
I discover COBAZ