NF ISO 13348
Fans - Tolerances, methods of conversion and technical data presentation
This document specifies performance tolerances and the technical data presentation for fans of all types. It does not apply for fans designed solely for low-volume air circulation, such as those used for household or similar purposes (ceiling and table fans, extractor fans, etc.). For jet fans, refer to ISO 13350.The upper limit of fan work per unit mass is normally 25 kJ/kg, corresponding to an increase of fan pressure of approximately 30 kPa for a mean density in the fan of 1,2 kg/m3. For higher values, agreement is to be reached between the supplier and the user.This document applies the five installation categories defined in ISO 5801: A free inlet, free outlet; B free inlet, ducted outlet; C ducted inlet, free outlet; D ducted inlet, ducted outlet; E free inlet and free outlet without a partition.The performance of a fan can vary considerably with the installation category it is operating within. Therefore, these categories form an important part of the definition of the fan?s technical data presentation.NOTE International acceptance of the five installation categories provides the opportunity to base a contract on the most appropriate fan category for the end user and the system designer. Correspondingly, the likelihood of the fan providing the agreed performance, without compromise or concession, is enhanced.The efficiency scaling procedures described in 8.1.5 apply to centrifugal fans and axial fans within the specific speed ranges shown in Table 4. To date, there is no experimental data to confirm how they apply to mixed flow fans, having specific speeds in between.Category E fans are treated in Clause 7.
This document specifies performance tolerances and the technical data presentation for fans of all types. It does not apply for fans designed solely for low-volume air circulation, such as those used for household or similar purposes (ceiling and table fans, extractor fans, etc.). For jet fans, refer to ISO 13350.
The upper limit of fan work per unit mass is normally 25 kJ/kg, corresponding to an increase of fan pressure of approximately 30 kPa for a mean density in the fan of 1,2 kg/m3. For higher values, agreement is to be reached between the supplier and the user.
This document applies the five installation categories defined in ISO 5801:
A free inlet, free outlet;
B free inlet, ducted outlet;
C ducted inlet, free outlet;
D ducted inlet, ducted outlet;
E free inlet and free outlet without a partition.
The performance of a fan can vary considerably with the installation category it is operating within. Therefore, these categories form an important part of the definition of the fan?s technical data presentation.
NOTE International acceptance of the five installation categories provides the opportunity to base a contract on the most appropriate fan category for the end user and the system designer. Correspondingly, the likelihood of the fan providing the agreed performance, without compromise or concession, is enhanced.
The efficiency scaling procedures described in 8.1.5 apply to centrifugal fans and axial fans within the specific speed ranges shown in Table 4. To date, there is no experimental data to confirm how they apply to mixed flow fans, having specific speeds in between.
Category E fans are treated in Clause 7.
ISO 13348:2007 specifies performance tolerances and the technical data presentation of industrial fans of all types. It does not apply for fans designed solely for low-volume air circulation, such as those used for household or similar purposes (ceiling and table fans, extractor fans, etc.). ISO 13348:2007 covers the four installation categories defined in ISO 5801: A, free inlet, free outlet; B, free inlet, ducted outlet; C, ducted inlet, free outlet; D, ducted inlet, ducted outlet.
- With a single click, add a new language, the Requirements or Redline+ service and add one or more additional users.
- Whether you are in the process of acquiring a standard or it is already available in your personal space, the UPSELL service is available at every stage to help you understand it and implement it within your organization.
COBAZ is the simple and effective solution to meet the normative needs related to your activity, in France and abroad.
Available by subscription, CObaz is THE modular solution to compose according to your needs today and tomorrow. Quickly discover CObaz!
Request your free, no-obligation live demo
I discover COBAZ