NF EN ISO 13792

NF EN ISO 13792

May 2013
Standard Cancelled

Thermal performance of buildings - Calculation of internal temperatures of a room in summer without mechanical cooling - Simplified methods

ISO 13792:2011 specifies the required input data for simplified calculation methods for determining the maximum, average and minimum daily values of the operative temperature of a room in warm periods: a) to define the characteristics of a room at the design stage in order to avoid overheating in summer; b) to define whether the installation of a cooling system is necessary or not.

View the extract
Main informations

Collections

National standards and national normative documents

Publication date

May 2013

Number of pages

67 p.

Reference

NF EN ISO 13792

ICS Codes

91.120.10   Thermal insulation of buildings

Classification index

P50-762

Print number

1 - 10/04/2013

International kinship

European kinship

EN ISO 13792:2012
Sumary
Thermal performance of buildings - Calculation of internal temperatures of a room in summer without mechanical cooling - Simplified methods

ISO 13792:2011 specifies the required input data for simplified calculation methods for determining the maximum, average and minimum daily values of the operative temperature of a room in warm periods:

a) to define the characteristics of a room at the design stage in order to avoid overheating in summer;

b) to define whether the installation of a cooling system is necessary or not.

Replaced standards (1)
NF EN ISO 13792
October 2005
Standard Cancelled
Thermal performance of buildings - Calculation of internal temperatures of a room in summer without mechanical cooling - simplified methods

<p>ISO 13792:2005 specifies the required input data for simplified calculation methods for determining the maximum, average and minimum daily values of the operative temperature of a room in the warm period to define the characteristics of a room in order to avoid overheating in summer at the design stage, and to define whether the installation of a cooling system is necessary or not.</p> <p>The criteria to be met by a calculation method in order to satisfy this standard are also given.</p>

Standard replaced by (2)
NF EN ISO 52016-1
July 2017
Standard Current
Energy performance of buildings - Energy needs for heating and cooling, internal temperatures and sensible and latent heat loads - Part 1 : calculation procedures

<p>ISO 52016-1:2017 specifies calculation methods for the assessment of:</p> <p>a) the (sensible) energy need for heating and cooling, based on hourly or monthly calculations;</p> <p>b) the latent energy need for (de-)humidification, based on hourly or monthly calculations;</p> <p>c) the internal temperature, based on hourly calculations;</p> <p>d) the sensible heating and cooling load, based on hourly calculations;</p> <p>e) the moisture and latent heat load for (de-)humidification, based on hourly calculations;</p> <p>f) the design sensible heating or cooling load and design latent heat load using an hourly calculation interval;</p> <p>g) the conditions of the supply air to provide the necessary humidification and dehumidification.</p> <p>The calculation methods can be used for residential or non-residential buildings, or a part of it, referred to as "the building" or the "assessed object".</p> <p>ISO 52016-1:2017 also contains specifications for the assessment of thermal zones in the building or in the part of a building. The calculations are performed per thermal zone. In the calculations, the thermal zones can be assumed to be thermally coupled or not.</p> <p>The calculation methods have been developed for the calculation of the basic energy loads and needs, without interaction with specific technical building systems, and for the calculation of the system specific energy loads and needs, including the interaction with specific systems. The hourly calculation procedures can also be used as basis for calculations with more extensive system control options.</p> <p>ISO 52016-1:2017 is applicable to buildings at the design stage, to new buildings after construction and to existing buildings in the use phase.</p> <p>NOTE Table 1 in the Introduction shows the relative position of ISO 52016-1:2017 within the set of EPB standards in the context of the modular structure as set out in ISO 52000-1.</p>

NF EN ISO 52017-1
July 2017
Standard Current
Energy performance of buildings - Sensible and latent heat loads and internal temperatures - Part 1 : generic calculation procedures

<p>ISO 52017-1:2017 specifies the general assumptions, boundary conditions and equations for the calculation, under transient hourly or subhourly conditions, of the internal temperatures (air and operative) and/or the heating, cooling and humidification and dehumidification loads to hold a specific (temperature, moisture) set point, in a single building zone. No specific numerical techniques are imposed by ISO 52017-1:2017.</p> <p>Specific calculation procedures based on the generic calculation procedures of ISO 52017-1:2017 are given in ISO 52016-1. The specific simplifications, assumptions and boundary conditions in ISO 52016-1 are tailored to the respective application areas, such as the energy need for heating and cooling and for humidification and dehumidification, hourly internal temperature, design heating and cooling and humidification and dehumidification load.</p> <p>NOTE Table 1 in the Introduction shows the relative position of ISO 52017-1:2017 within the set of EPB standards in the context of the modular structure as set out in ISO 52000-1.</p>

Table of contents
View the extract
  • Avant-propos
    iv
  • Introduction
    vi
  • 1 Domaine d'application
    1
  • 2 Références normatives
    1
  • 3 Termes, définitions, symboles et unités
    2
  • 3.1 Termes et définitions
    2
  • 3.2 Symboles et unités
    3
  • 3.3 Indices
    6
  • 4 Données d'entrée et résultats
    6
  • 4.1 Hypothèses
    6
  • 4.2 Conditions aux limites et données d'entrée
    7
  • 4.3 Données de sortie
    12
  • 5 Méthode de calcul
    12
  • 6 Méthodes de validation
    12
  • 6.1 Introduction
    12
  • 6.2 Validation de la méthode de calcul
    13
  • 6.3 Validation du facteur d'affaiblissement du rayonnement solaire dû aux obstacles extérieurs
    19
  • Annexe A (informative) Exemples de modèle de résolution
    23
  • Annexe B (informative) Renouvellements d'air pour la ventilation naturelle
    40
  • Annexe C (informative) Évaluation de la zone ombrée d'une surface plane due aux obstacles extérieurs
    42
  • Annexe D (informative) Apports internes
    45
  • Annexe E (informative) Exemples de calcul
    47
  • Annexe F (informative) Références normatives à des publications internationales avec publications européennes correspondantes
    56
Need to identify, monitor and decipher standards?

COBAZ is the simple and effective solution to meet the normative needs related to your activity, in France and abroad.

Available by subscription, CObaz is THE modular solution to compose according to your needs today and tomorrow. Quickly discover CObaz!

Request your free, no-obligation live demo

I discover COBAZ