NF EN ISO 13792
Thermal performance of buildings - Calculation of internal temperatures of a room in summer without mechanical cooling - Simplified methods
ISO 13792:2011 specifies the required input data for simplified calculation methods for determining the maximum, average and minimum daily values of the operative temperature of a room in warm periods: a) to define the characteristics of a room at the design stage in order to avoid overheating in summer;b) to define whether the installation of a cooling system is necessary or not.
ISO 13792:2011 specifies the required input data for simplified calculation methods for determining the maximum, average and minimum daily values of the operative temperature of a room in warm periods:
a) to define the characteristics of a room at the design stage in order to avoid overheating in summer;
b) to define whether the installation of a cooling system is necessary or not.
ISO 13792:2005 specifies the required input data for simplified calculation methods for determining the maximum, average and minimum daily values of the operative temperature of a room in the warm period to define the characteristics of a room in order to avoid overheating in summer at the design stage, and to define whether the installation of a cooling system is necessary or not. The criteria to be met by a calculation method in order to satisfy this standard are also given.
ISO 52016-1:2017 specifies calculation methods for the assessment of: a) the (sensible) energy need for heating and cooling, based on hourly or monthly calculations; b) the latent energy need for (de-)humidification, based on hourly or monthly calculations; c) the internal temperature, based on hourly calculations; d) the sensible heating and cooling load, based on hourly calculations; e) the moisture and latent heat load for (de-)humidification, based on hourly calculations; f) the design sensible heating or cooling load and design latent heat load using an hourly calculation interval; g) the conditions of the supply air to provide the necessary humidification and dehumidification. The calculation methods can be used for residential or non-residential buildings, or a part of it, referred to as "the building" or the "assessed object". ISO 52016-1:2017 also contains specifications for the assessment of thermal zones in the building or in the part of a building. The calculations are performed per thermal zone. In the calculations, the thermal zones can be assumed to be thermally coupled or not. The calculation methods have been developed for the calculation of the basic energy loads and needs, without interaction with specific technical building systems, and for the calculation of the system specific energy loads and needs, including the interaction with specific systems. The hourly calculation procedures can also be used as basis for calculations with more extensive system control options. ISO 52016-1:2017 is applicable to buildings at the design stage, to new buildings after construction and to existing buildings in the use phase. NOTE Table 1 in the Introduction shows the relative position of ISO 52016-1:2017 within the set of EPB standards in the context of the modular structure as set out in ISO 52000-1.
ISO 52017-1:2017 specifies the general assumptions, boundary conditions and equations for the calculation, under transient hourly or subhourly conditions, of the internal temperatures (air and operative) and/or the heating, cooling and humidification and dehumidification loads to hold a specific (temperature, moisture) set point, in a single building zone. No specific numerical techniques are imposed by ISO 52017-1:2017. Specific calculation procedures based on the generic calculation procedures of ISO 52017-1:2017 are given in ISO 52016-1. The specific simplifications, assumptions and boundary conditions in ISO 52016-1 are tailored to the respective application areas, such as the energy need for heating and cooling and for humidification and dehumidification, hourly internal temperature, design heating and cooling and humidification and dehumidification load. NOTE Table 1 in the Introduction shows the relative position of ISO 52017-1:2017 within the set of EPB standards in the context of the modular structure as set out in ISO 52000-1.
- Avant-proposiv
- Introductionvi
-
1 Domaine d'application1
-
2 Références normatives1
-
3 Termes, définitions, symboles et unités2
-
3.1 Termes et définitions2
-
3.2 Symboles et unités3
-
3.3 Indices6
-
4 Données d'entrée et résultats6
-
4.1 Hypothèses6
-
4.2 Conditions aux limites et données d'entrée7
-
4.3 Données de sortie12
-
5 Méthode de calcul12
-
6 Méthodes de validation12
-
6.1 Introduction12
-
6.2 Validation de la méthode de calcul13
-
6.3 Validation du facteur d'affaiblissement du rayonnement solaire dû aux obstacles extérieurs19
- Annexe A (informative) Exemples de modèle de résolution23
- Annexe B (informative) Renouvellements d'air pour la ventilation naturelle40
- Annexe C (informative) Évaluation de la zone ombrée d'une surface plane due aux obstacles extérieurs42
- Annexe D (informative) Apports internes45
- Annexe E (informative) Exemples de calcul47
- Annexe F (informative) Références normatives à des publications internationales avec publications européennes correspondantes56
COBAZ is the simple and effective solution to meet the normative needs related to your activity, in France and abroad.
Available by subscription, CObaz is THE modular solution to compose according to your needs today and tomorrow. Quickly discover CObaz!
Request your free, no-obligation live demo
I discover COBAZ